AISERVA and AIKuari · AISERVA and AIKuari: Local AI Guide
Alarms
VYROX Wiki · Updated 23 September 2026 · https://www.vyrox.com/wiki/aikuari-alarms
Alarms in VYROX Quarry (AIKuari) tell a person when a reading crosses a warning or alarm limit, when a trend is projected to reach its limit, or when a rule fires. Each alarm appears as a banner and in the alarm list, and a person acknowledges it with an optional note. Control rooms, plant managers and engineers work the alarm list every shift.
Severity Levels
The demo shows three severity badges.
Level
Meaning
Sample Alarm
Warning
A reading or projection needs attention
"Hot idler on CV2: 68 °C, 34 °C over its neighbours"
Serious
A reading is well past its trigger
"PM10 178 µg/m³ at the village-side monitor, over the 150 trigger"
Critical
The most urgent level
Set per site with VYROX
A prediction alarm is raised when a trend is projected to reach its alarm limit within 7 days. See Machine Condition and Work Orders.
Where Alarms Appear
A banner slides in when a new alarm is raised, showing the severity, site and title. Press the X to dismiss it; it also leaves by itself after a few seconds.
The bell button at the top of the screen shows the number of open alarms and opens Alarms.
The Alarms item in the sidebar shows the open count.
The Open Alarms card on Group View.
How Alarms Behave
The How Alarms Behave card on the Alarms screen sets out the rules:
Warning and alarm limits use an ISA-18.2 style deadband: a reading must fall a clear 2 % inside the limit to return.
An alarm that returns before anyone acknowledges it stays on the list.
A prediction alarm is raised when a trend is projected to reach its limit within 7 days.
Every acknowledgement, with its note, goes to the audit log.
Acknowledge an Alarm
Open Alarms from the Operations group, or press the bell button.
Read the alarm: severity, title, site, the time since it was raised, and any detail line.
Optionally type in the Note (Optional) box, for example what you checked or who you sent.
Press Acknowledge. The alarm is marked as acknowledged and the open count drops.
Alarms Seen in the Demo Day
Module
Sample Alarm
Machine Condition
Bearing temperature projected to reach 85 °C within 7 days, or over the 75 °C warning limit
Conveyors
Hot idler, hotter than its neighbours
Environment
PM10 over the dust trigger at the village-side monitor
Loading and Delivery
A load predicted to arrive below the minimum temperature
The product also describes alarms for blasts over the limit and for asphalt plant readings; these do not fire in the demo day.
Frequently Asked Questions
Why Is an Alarm Still Listed After the Reading Went Back to Normal?
An alarm that returns before anyone acknowledges it stays on the list, so nothing is missed.
Where Are the Limits Set?
On the Limits page, set up with VYROX for your site. A limit that is not yet confirmed is marked as unconfirmed on screen.
Does an Alarm Stop the Machine?
No. Nothing in VYROX Quarry stops plant by itself.